EN
+8620-89856705

Large air flow box filter

Features
  • Large dust holding capacity and high filtration efficiency;
  • Large air volume and low resistance;
  • Solid and beautiful structure.
Applications
Mainly used in the secondary or back-end filtration of various ventilation systems, air conditioning systems and dust removal systems with large air volume requirements.
Send inquiry

Size

Rated air flow (m³/h)

Initial resistance(Pa)

Final Resistance(Pa)

Filter particle(μm)

Filtration efficiency (%)

Filter grade

592*592*292

2200/4400

<30/60

<320

≥1

45%

F5

287*592*292

1100/2200

<30/60

<320

≥1

45%

F5

592*592*150

1800/3600

<30/60

<320

≥1

45%

F5

287*592*150

1000/1800

<30/60

<320

≥1

45%

F5

592*592*292

2200/4400

<40/75

<320

≥1

65%

F6

287*592*292

1100/2200

<40/75

<320

≥1

65%

F6

592*592*150

1800/3600

<40/75

<320

≥1

65%

F6

287*592*150

1000/1800

<40/75

<320

≥1

65%

F6

592*592*292

2200/4400

<50/85

<320

≥1

85%

F7

287*592*292

1100/2200

<50/85

<320

≥1

85%

F7

592*592*150

1800/3600

<50/85

<320

≥1

85%

F7

287*592*150

1000/1800

<50/85

<320

≥1

85%

F7

592*592*292

2200/4400

<55/95

<320

≥1

90%

F8

287*592*292

1100/2200

<55/95

<320

≥1

90%

F8

592*592*150

1800/3600

<55/95

<320

≥1

90%

F8

287*592*150

1000/1800

<55/95

<320

≥1

90%

F8

592*592*292

2200/4400

<65/105

<320

≥1

95%

F9

287*592*292

1100/2200

<65/105

<320

≥1

95%

F9

592*592*150

1800/3600

<65/105

<320

≥1

95%

F9

287*592*150

1000/1800

<65/105

<320

≥1

95%

F9


Related Products